EasyMarker E-Stop Suggestions
Q:
To summarize:
The system worked in the =
past.CMT recently did service on the marker and =
controller.When marker was returned, it worked when hooked up to a =
laptop at your desk.When connected to a PLC and other I/O =
in your production cell, problems occurred.
E-Stop issues:
The E-stop screen alarm on the =
EasyMarker is displayed.The signal from the PLC estop string =
is high (on).The Marker’s reset function will not clear the alarm. =
Program start function:
The PLC program initiate signal will =
not start the marker’s program.
A: =
Suggestions:
1.) =
Try to turning on/off the option-bits for in the =
Marker:
– =
E-stop (19) ON
– =
Remote Reset (20) ON
– =
Program Start (17) ON
– =
This should help to isolate if it’s a =
marker problem in the Estop string.
2.) =
Try forcing turning ON in the PLC the input for =
Marker Ready:
– =
You will have to manually start the =
program.
– =
This may help determine if the chain of events =
(other prox switches and signals in the system) necessary to =
“authorize” the marker to start are working and in the =
correct order.
The =
EasyMark Operator Guide has an excellent I/O setup in chapter-3 (pages =
10-11)